Application The DDS76 differential pressure switch takes over control of the reverse rinsing operation on the Honeywell F76, F76S and F76S-F filters in conjunction with an automatic reverse rinsing actuator with volt-free contacts.
Special Features • Easy setting of the differential pressure • Simple assembly
Range of Application Medium : Water Setting range : 0.1 to 1.6 bar (set at 1.0 bar during manufacture)
Technical Data Cable : 1 meter with connector bush Maximum static pressure* : 25.0 bar Maximum static operating pressure* : 16.0 bar Maximum permissible temperature of medium : + 70 ¡ÆC Maximum permissible ambient temperature : + 80 ¡ÆC Microswitch ysteresis : Approximately 2 % Maximum microswitch loading : Umax = 24 V , Imax = 0.8 A , Pmax = 19.2 W |